Frequently Asked Questions
Things we get asked a lot
AS/NZS 3760:2022 Electrical Safety Standard is the relevant standard for the safety inspection and testing of electrical appliances
All electrical items designed for connection by flexible supply cord and plug top to 240v or 415v power need to be inspected, tested, and tagged in every type of workplace, organisation, or community centre.
The following items are excluded from testing and tagging under AS/NZS 3760:2022:
Fixed or hard-wired items
Items at a height exceeding 2.5 meters
Items that need to be dismantled to establish safety
Demonstration items or new stock in a retail or warehouse outlet
All portable plug-in appliances and electrical plug-in appliances located in your workplace and plugged into a power point situated less than 2.5m from the ground require inspection, testing, and tagging.
For example, the following items require testing and tagging:
Laptop computers
Desktop computers and monitors
Printers
Photocopiers
Fax machines
Staff kitchen and tea room appliances
All electric power tools
Extension cords
Power boards
IEC leads
All double insulated appliances
Audio/visual equipment
Portable air conditioners
Isolation transformers
Desk lamps
Vacuum cleaners and electrical cleaning equipment
Forklift chargers
3-phase electrical equipment
RCDs – Safety Switch
Under the standard, the following basic tests may be conducted on each appliance:
Visual inspection
Insulation resistance
Earth continuity
Polarity
Earth leakage
Test and Tag Colours WA
For the construction, demolition and mining industry the colour of the tags does matter. Refer to the list below for the current test and tag colours in Western Australia.
The quarterly test and tag colours are:
RED
December, January , February
GREEN
March, April, May
BLUE
June, July, August
YELLOW
September, October, November
For construction sites the colour of the tag should identify the period in which the test was conducted. For example items tested in the September - November quarter should have yellow tags applied. The test is valid for 3 months, irrespective of whether it goes into the next period (which will generally be the case). In the following period you will often see the previous colour tags, but as long as they are still within 3 months they are valid, and meet the requirements of the Australian Standard.
For all other industries the colour of the tags are not regulated.
Yes we do! Our electrical compliance report provides the results and details of each test conducted. In order to ensure that the information is available when required, it is vital all test results are properly recorded. Here at Treaty Test and Tag our reports are provided in a PDF format via email or hard copy if requested.
It is recommend you keep any electrical report for at least the lifetime the equipment is in use. The electrical test and tag log can be used as part of risk assessment for your workplace.